UPS Web/SNMP Card
UPSLink
User Guide
Version 2.2.3
2007-05-07
Przeglądanie stron 0
1 2 3 4 5 6 ... 53 54

Podsumowanie treści

Strona 1 - User Guide

1UPS Web/SNMP CardUPSLinkUser GuideVersion 2.2.32007-05-07

Strona 2 - Technical Support

102. Getting StartedThis chapter describes how to set up and configure the UPSLink.- 0 Panel layout explains the layout of the panel and LED indicator

Strona 3 - Revision history

11Lamps FunctionPower Turned on if power is suppliedReady Turned on if system is ready to runSerial Rx/Tx Blink whenever there is any incoming or outg

Strona 4 - Contents

12The [Link] lamp will light up green.The [Act] lamp will blink to indicate incoming/outgoing Ethernet packetsThe [100Mbps] lamp will light up green i

Strona 5

132.3 Accessing the UPSLinkThere are several ways to access the UPSLink. These methods are dependent on whether the user islocated at a local site or

Strona 6 - 1. Introduction

14Welcome to UPSLink ConfigurationPress EnterLogin : adminPassword : *****----------------------------------------------------------------------------

Strona 7 - 1.3 Product specification

15Or run a Telnet program with the following parameters:Figure 0-6 Telnet program set up example (TeraTerm Pro)2) The user must log into the UPSLink.

Strona 8

16Figure 0-7 Login screen of the UPSLink Web ManagementFigure 0-8 shows the user homepage of the UPSLink Web management interface. A menu bar isprovid

Strona 9 - Table 0-1 Acronym Table

173. UPS management3.1 UPS informationOnce the UPSLink is connect to a UPS and communicates with the UPS through serial connection,the basic informati

Strona 10 - 2. Getting Started

183.2 UPS statusIf there occurred any UPS alarms, the alarm records are shown on this page in red-colored font withtheir detected time. The informatio

Strona 11 - 2.2 Connecting hardware

19Figure 0-3 UPS status diagram3.4 UPS graphics – gaugeA dedicated java applet communicates with UPSLink continuously through a separate TCP port (TCP

Strona 12

2User Guide for the UPSLinkVersion 2.2.3Firmware version 2.2.xPrinted in KoreaCopyright InformationCopyright 2002-2007, Sena Technologies, Inc. All ri

Strona 13 - 2.3 Accessing the UPSLink

20The users may navigate between Battery, Input, Output and Bypass group by pressing buttons at thetop of the applet.Figure 0-5 UPS status gauge – Inp

Strona 14 - 2.3.2 Using Telnet

213.6 UPS controlBesides the parameter configurations, the commands that control the UPS directly such as tests,shutdown, restart and reboot are offer

Strona 15 - 2.4 Accessing web Interface

22Alarm emails are sent in two forms, brief or detailed. Detailed messages contain additional UPS statusinformation to the alarm information.Figure 0-

Strona 16

234. Network configuration4.1 IP configurationThe UPSLink requires a valid IP address to operate within the user’s network environment. If the IPaddre

Strona 17 - 3. UPS management

244.1.1 Using static IP addressWhen using a Static IP address, the user must manually specify all the configuration parametersassociated with the UPSL

Strona 18 - 3.2 UPS status

25The IP address of the DNS server must be able to access the host site with the provided domainname. The UPSLink provides the ability to configure th

Strona 19 - 3.4 UPS graphics – gauge

26in the DHCP network, the administrator needs the MAC address of the UPSLink found on the labelsticker at the bottom of the UPSLink.4.1.3 Using PPPoE

Strona 20 - 3.5 UPS configuration

27Figure 0-2 SNMP configuration4.2.1 MIB-II system objects configurationMIB–II System objects configuration sets the System Contact, Name, Location, a

Strona 21 - 3.7 UPS alarm log

284.2.2 Access control configurationAccess Control defines accessibility of managers to the UPSLink SNMP agent. Only a manager fromthe specified NMS c

Strona 22 - 3.8 UPS serial program

2918 A general fault in the UPS has been detected.19 The result of the last diagnostic test indicates a failure.20 A problem has been encountered in t

Strona 23 - 4. Network configuration

3Revision historyDate Part number Description2003-04-30 V2.0.0 written by UIS2003-05-02 V2.0.1 revise candidate by KCY,2003-05-13 V2.0.2 revised done

Strona 24 - 4.1.1 Using static IP address

30To use the Dynamic DNS service provided by Dynamic DNS Network Services, the user must set upan account in their Members' NIC (Network Informat

Strona 25 - 4.1.2 Using DHCP

31Consequently, the email address set for the device can use an arbitrary username with a registeredhostname (i.e. [email protected] or anybody

Strona 26 - 4.2 SNMP configurations

32Figure 0-5 Access control configurationA user may specify more than one host as allowed to configure the UPSLink. The user must thenenter the IP add

Strona 27

33Figure 0-6 SYSLOG server configurationTo receive log messages from the UPSLink, the SYSLOG server specified in the UPSLink’sconfiguration must be co

Strona 28

34information about the configuration of the UPS alarm and system log storage location, please refer tosection 0. 3.7 UPS alarm log and 0. 6.2 System

Strona 29 - 4.3 Dynamic DNS configuration

355. Serial port configuration5.1 UART configurationTo connect the UPS to the UPSLink serial port, the serial port parameters of the UPSLink shouldmat

Strona 30 - 4.4 SMTP configuration

366. System status and logThe UPSLink displays the system status and the log data. The UPSLink can also be configured todeliver system log data daily

Strona 31 - 4.5 Access control

37the user must set parameters to initiate the creation of an email. These parameters would include thetime to trigger an email by hour, the recipient

Strona 32

387. System administrationThe UPSLink utilizes three user profile types to control accessibility to different functions. Thesethree levels of user typ

Strona 33 - 4.7 NFS server configuration

39The user groups and their UPSLink access privileges for management web pages are summarized inthe Table 0-2.Group System Administrator UPS Administr

Strona 34 - 4.8 Ethernet configuration

4Contents1. Introduction 61.1 Overview...

Strona 35 - 5. Serial port configuration

40Figure 0-2 Adding a userFigure 0-3 shows the [Change password] screen.Figure 0-3 Changing the passwordFigure 0-4 shows the [remove a user] screen.Fi

Strona 36 - 6. System status and log

417.3 LanguageThe users of the UPSLink can switch language of the management web pages. Currently the UPSLinksupports two language sets, English and K

Strona 37

427.5 Factory default resetA user may restore the factory default settings at any time by selecting “Factory reset”or by pushingthe factory default re

Strona 38 - 7. System administration

43To use either a Telnet or serial console to upgrade your firmware, the Telnet or terminal emulationprogram must support Zmodem transfer protocol.To

Strona 39

44Figure 0-11Transfer binary file by Zmodem (HyperTerminal)-------------------------------------------------------------------------------System Admin

Strona 40 - 7.2 Device name configuration

45Appendix A. ConnectionsA.1 Ethernet pin outsThe UPSLink uses the standard Ethernet connector that is shielded connector compliant withAT&T258 sp

Strona 41 - 7.4 Date and time settings

46A.3 Ethernet wiring diagramFigure 0-3 Ethernet direct connection using crossover Ethernet cableFigure 0-4 Ethernet connection using straight through

Strona 42 - 7.6 Firmware upgrade

47Appendix B. Well-known port numbersPort numbers are divided into three ranges: Well Known Ports, Registered Ports, and Dynamic and/orPrivate Ports.

Strona 43

48Appendix C. Guide to the Bootloader menu programC.1 OverviewThe bootloader menu provides a way to recover the UPSLink using BOOTP/TFTP as a disaster

Strona 44

49until the user presses the <ctrl-c> keys. In this mode, the ping test to the remote host (server IPaddress) and UART test are not performed.If

Strona 45 - Appendix A. Connections

54.4 SMTP configuration...304.5 Access cont

Strona 46 - A.4 Serial wiring diagram

504. EEPROM test5. Ethernet test<ESC> Back, <ENTER> Refresh----->Figure 0-2 Hardware test menu within Bootloader Menu ProgramWhen the u

Strona 47

515. Ethernet test<ESC> Back, <ENTER> Refresh-----> 1******* Hardware auto-detect and auto-test *******[DRAM]DRAM Test in progress ----

Strona 48 - C.3 Hardware test menu

52-------------------------------------------------------------------------------Firmware upgrade-----------------------------------------------------

Strona 49

53Appendix D. WarrantyD.1 GENERAL WARRANTY POLICYSena Technologies, Inc. (hereinafter referred to as SENA) warrants that the Product shall conform toa

Strona 50

54D.3 HARDWARE PRODUCT WARRANTY DETAILSWARRANTY PERIOD: SENA warranties embedded hardware Product for a period of one (1) year,and external hardware P

Strona 51 - C.4 Firmware upgrade menu

61. Introduction1.1 OverviewThe UPSLink is an embedded Linux-based Web/SNMP card for UPS. The UPSLink provides SNMP,HTTP and Telnet compatibility allo

Strona 52

71.2 Package check listUPSLink100:- 110~230 VDC power adaptor- Serial console cable- CD-ROM, including software andmanuals1.3 Product specificationSma

Strona 53 - Appendix D. Warranty

8EnvironmentalOperating temperature: 0 ~ 50oCStorage temperature: -20~ 66oCHumidity: 90% Non-condensingPower 5VDC, 1.5A @ 5VDimensionL x W x H100 x 72

Strona 54

9ISP Internet Service ProviderPC Personal ComputerNIC Network Interface CardMAC Media Access ControlLAN Local Area NetworkUTP Unshielded Twisted PairA